Aluminium Conductors

ALL ALUMINIUM CONDUCTORS

All aluminium conductors, AAC for low voltage (LV) distribution overhead lines are usually manufactured to meet TS-IEC 1089.
Sizes and stranding in accordance with other specifications as CSA, DIN, BS, SFS, NF or customer’s specifications will be manufactured by request.
Standard wooden reels are normally non-returnable, for dimensions see table below.

STANDARD TYPE WOODEN DRUMS DIMENSIONS FOR CONDUCTORS


TYPE OF
REELS

DIMENSIONS(mm)

WEIGHT
(kg)

VOLUME
(m³)

A B C D E

TA

1000 810 480 720 85 104 1.00
D 1180 810 580 720 85 110 1.50
EH 1500 865 760 733 85 212 2.20
GR 2000 1120 900 940 85 640 4.80

resimhalilyeni2.JPG (10386 bytes) MARKING

Manufacturer name, manufacturing year and standard, conductor type, name, nominal cross-section, overall diameter, number x length, order name and code, brut and net weight of the reel are marked on a metallic etiquette which is on the reel side.

The transportation direction showed by an arrow on the reel side.

 

ALL ALUMINIUM CONDUCTORS  (AAC)-Construction, mechanical and electrical properties


 
 

CSA
Code

Word

A1
(Al)
mm2

Nominal Area

Cupper
Equivalent

Area
mm²

Wire Diameter and no.

Complete
Conductor
Diameter

mm

DC
Resistanse
at  20º C

Ohm/km

AWG
or
cir.mils

Complete
Conductor

mm²

Aluminium

No.

Diam.
mm

ROSE

21

4

21,14

13,30

7

1,96

5,88

1.354

LILY

27

3

26,66

16,78

7

2,20

6,61

1.074

PANSY

42

1

42,37

26,57

7

2,78

8,33

0,6752

POPPY

53

1/0

53,49

33,73

7

3,12

9,36

0,5351

ASTER

67

2/0

67,45

42,32

7

3,50

10,51

0,4245

PHLOX

85

3/0

84,99

53,52

7

3,93

11,80

0,3366

OXLIP

107

4/0

107,3

67,50

7

4,42

13,25

0,2671

 
 

CSA
Code Word

 

A1 (Al)
mm2

Nominal Area

Rated Tension
Srenght
kgf

 

Nominal
Weight
kg/km

Standard Shipment

Ampacity of conductor

AWG
or
cir.mils

Complete
Conductor
mm²

Conductor
No.xlength
m

Net
Weight
kg

Type
of reel

AMPERES

(1)          (2)        (3)

ROSE

21

4

21,14

403

58

1x10000

580

TA

110

140

150

LILY

27

3

26,66

495

73

1x7700

565

TA

125

160

170

PANSY

42

1

42,37

725

116

1x5000

580

TA

165

200

230

POPPY

53

1/0

53,49

888

146

1x3800

555

TA

193

230

270

ASTER

67

2/0

67,45

1115

184

1x3100

570

TA

225

260

300

PHLOX

85

3/0

84,99

1369

232

1x2500

580

TA

262

300

340

OXLIP

107

4/0

107,3

1732

294

1x1900

560

TA

306

370

400

   AMPACITY FACTORS

1

2

3

4

5

6

  Wind velocity

m/sec

0

0,6096

0,6

0,6

0,6

0,6

  Ambient Temperature

ºC

40

25

20

45

35

25

  Max. Temperature of
  conductor

ºC

80

75

80

80

80

80

  Frequency

Hz

50

60

50

50

50

50

  Surface of conductor

  

-

mat

  Sun Radiation

kW/m²

-

-

1

1,2

1,2

1,2